web statistics
  • LRS-200-4.2


Mean Well Authorized Distributor since 1997

Model No. - LRS-200 Series

Max Output Wattage (W) - 100 Watts

Output Voltage (VDC) – 3.3, 4.2, 5, 12, 15, 24, 36, 48 Volts

Model No.

LRS-200-3.3

LRS-200-4.2

LRS-200-5

LRS-200-12

LRS-200-15

LRS-200-24

LRS-200-36

LRS-200-48

Output: 

DC Voltage

3.3V

4.2V

5V

12V

15V

24V

36V

48V

Rated Current

40A

40A

40A

17A

14A

8.8A

5.9A

4.4A

Current Range

0 ~ 40A

0 ~ 40A

0 ~ 40A

0 ~ 17A

0 ~ 14A

0 ~ 8.8A

0 ~ 5.9A

0 ~ 4.4A

Rated Power

132W

168W

200W

204W

210W

211.2W

212.4W

211.2W

Ripple & Noise (max.) Note 2

150mVp-p

150mVp-p

150mVp-p

150mVp-p

150mVp-p

150mVp-p

200mVp-p

200mVp-p

Voltage ADJ. Range

2.97 ~ 3.6V

3.6 ~ 4.4V

4.5 ~ 5.5V

10.2 ~ 13.8V

13.5 ~ 18V

21.6 ~ 28.8V

32.4 ~ 39.6V

43.2 ~ 52.8V

Voltage Tolerance Note 3

±3.0%

±4.0%

±3.0%

±1.5%

±1.0%

±1.0%

±1.0%

±1.0%

Line Regulation Note 4

±0.5%

±0.5%

±0.5%

±0.5%

±0.5%

±0.5%

±0.5%

±0.5%

Load Regulation Note 5

±2.5%

±2.5%

±2.0%

±1.0%

±0.5%

±0.5%

±0.5%

±0.5%

Setup, Rise Time

1300ms, 50ms/230VAC        1300ms, 50ms/115VAC at full load

Hold up Time

16ms / 230VAC        12ms/115VAC at full load

Input:

Voltage Range

90~132VAC /180 ~ 264VAC by switch     240 ~ 370VDC    (switch on 230VAC)          

Frequency Range

47~63Hz

Efficiency (Typ.)

83%

86%

87%

87.5%

88%

89.5%

89.5%

90%

AC Current (Typ.)

4A/115VAC               2.2A/230VAC

Inrush Current (Typ.)

COLD START 60A/230VAC

Leakage Current

<2mA / 240VAC

Protection:

Over Load

110 ~ 140% rated output power

Protection type : Hiccup mode, recovers automatically after fault condition is removed

Over Voltage

3.8 ~ 4.45V

4.6 ~ 5.4V

5.75 ~ 6.75V

13.8 ~ 16.2V

18.75 ~ 21V

28.8 ~ 33.6V

41.4 ~ 46.8V

55.2 ~ 64.8V

Protection type: Shut down o/p voltage, re-power on to recover

 

Environment:

Working Temp.

-25 ~ +70°C (Refer to "Derating Curve")

Working Humidity

20 ~ 90% RH non-condensing

Storage Temp., Humidity

-40 ~ +85°C, 10 ~ 95% RH

Temp. Coefficient

±0.03%/°C (0 ~ 50°C)

Vibration

10 ~ 500Hz, 5G 10min. / 1cycle 60 min. each along X, Y, Z axes

Safety & EMC

Safety Standards

UL60950-1 approved

Withstand Voltage

I/P - O/P : 3KVAC     I/P-FG : 2KVAC      O/P-FG : 0.5KVAC

Isolation Resistance

I/P - O/P, I/P-FG, O/P-FG : 100M Ohms / 500VDC / 25°C / 70% RH

Others:

MTBF

347.5Khrs min.    MIL-HDBK-217F (25°C)

Dimension

215*115*30mm (L*W*H)

Packing

0.66Kg; 15pcs / 10.9Kg / 0.78CUFT

 

Electrical Specifications
Dimensions 8.5 x 4.5 x 1.9 in (L*W*H)
Input Voltage 85~264VAC
Number of Outputs 1
Output Voltage 4.2V
PDF Specs View Spec Sheet
Wattage 108
General
Industry Aliases new

LRS-200-4.2

  • Brand: Mean Well
  • Product Code: LRS-200-4.2
  • Availability: Call for Availability
  • $33.80

  • Ex Tax: $33.80

©2024 Peak to Peak Power, Inc. All Rights Reserved. Marketing by Digital Lightbridge.